RASE Compliance Document Examples

HTML Example

<!DOCTYPE html>
<html xmlns="http://www.w3.org/1999/xhtml">
    <head>
        <title>The Building Regulations 2010 - Fire Safety - Approved Document B  - Volume 2: Buildings
         other than dwellings
      </title>
        <meta charset="UTF-8"/>
        <meta name="ckterms:projectStage" content="CIC 4: Technical design"/>
        <meta name="dcterms:coverage.temporal" content="2020-11-26"/>
        <meta name="dcterms:coverage.spatial" content="GB-ENG"/>
        <meta name="dcterms:dateCreated" content="2019-01-01"/>
        <meta name="dcterms:modified" content="2020-11-26"/>
        <meta name="ckterms:accessLocation" content="TBC"/>
        <meta name="dcterms:identifier" content="hJJ3qCORuUmX8LWK0_SZQQ"/>
        <meta name="dcterms:language" content="en-gb"/>
        <meta name="ckterms:version" content="1.0"/>
    <meta name="ckterms:sector" content="Uniclass2015: Administrative, commercial and protective service entities"/>
    <meta name="ckterms:sector" content="Uniclass2015: Cultural, educational, scientific and information entities"/>
    <meta name="ckterms:sector" content="Uniclass2015: Industrial entities"/>
    <meta name="ckterms:sector" content="Uniclass2015: Water and land management entities"/>
    <meta name="ckterms:sector" content="Uniclass2015: Medical, health, welfare and sanitary entities"/>
    <meta name="ckterms:sector" content="Uniclass2015: Recreational entities"/>
    <meta name="ckterms:sector" content="Uniclass2015: Sport and activity entities"/>
    <meta name="ckterms:sector" content="Uniclass2015: Waste disposal entities"/>
    <meta name="ckterms:sector" content="Uniclass2015: Piped supply entities"/>
    <meta name="ckterms:sector" content="Uniclass2015: Heating, cooling and refrigeration entities"/>
    <meta name="ckterms:sector" content="Uniclass2015: Ventilation and air conditioning entities"/>
    <meta name="ckterms:sector" content="Uniclass2015: Electrical power generation and distribution entities"/>
    <meta name="ckterms:sector" content="Uniclass2015: Communications, security, safety and protection entities"/>
    <meta name="ckterms:sector" content="Uniclass2015: Transport entities"/>
    <meta name="ckterms:sector" content="Uniclass2015: Circulation and storage entities"/>
    <meta name="dcterms:subject" content="Uniclass2015: Administrative, commercial and protective service entities"/>
    <meta name="dcterms:subject" content="Uniclass2015: Cultural, educational, scientific and information entities"/>
    <meta name="dcterms:subject" content="Uniclass2015: Industrial entities"/>
    <meta name="dcterms:subject" content="Uniclass2015: Water and land management entities"/>
    <meta name="dcterms:subject" content="Uniclass2015: Medical, health, welfare and sanitary entities"/>
    <meta name="dcterms:subject" content="Uniclass2015: Recreational entities"/>
    <meta name="dcterms:subject" content="Uniclass2015: Sport and activity entities"/>
    <meta name="dcterms:subject" content="Uniclass2015: Waste disposal entities"/>
    <meta name="dcterms:subject" content="Uniclass2015: Piped supply entities"/>
    <meta name="dcterms:subject" content="Uniclass2015: Heating, cooling and refrigeration entities"/>
    <meta name="dcterms:subject" content="Uniclass2015: Ventilation and air conditioning entities"/>
    <meta name="dcterms:subject" content="Uniclass2015: Electrical power generation and distribution entities"/>
    <meta name="dcterms:subject" content="Uniclass2015: Communications, security, safety and protection entities"/>
    <meta name="dcterms:subject" content="Uniclass2015: Transport entities"/>
    <meta name="dcterms:subject" content="Uniclass2015: Circulation and storage entities"/>
        <meta name="dcterms:type" content="Guidance"/>
        <link href="rase.css" rel="stylesheet" type="text/css"/>
    </head>
    <body>
        <section data-identifier="hSGB1-fufEiacSuJk8k62g" data-numbered="global" title="Fire detection and alarm systems">
            <section data-identifier="xwvgHCgydk2g0xOXFUUBDg"  title="General provisions">
                <p data-numbered="global" data-identifier="XhhBpnB4OEK7hIT65pL2Dg">
                    <span data-raseType="RequirementSection" id="R1">All <span data-raseType="Application" id="a1" data-raseProperty="building">buildings</span> should have arrangements for <span data-raseType="Requirement" id="r11" data-raseProperty="fire detecting arrangements">detecting fire</span> and <span data-raseType="Requirement" id="r12" data-raseProperty="arrangements for raising the alarm">raising the alarm</span>. </span> In most buildings, fires are detected by people, either by sight or smell, and therefore
                  often nothing more is needed.
            </p>
                <p data-numbered="global" data-identifier="mmIg3jdJQkmPzlyZVjPE7g">In some small buildings/premises, the means of raising the alarm may be simple (for
               example,a
               shouted warning). In assessing appropriate solutions, warnings need to be heard and
               understood
               throughout the premises.
            </p>
            </section>
            <section data-identifier="MSriiQXQn0uDeengQVGHLA"  title="Fire detection and alarm systems">

        <p data-numbered="global" data-identifier="KKS5C-JUdUOJBvGxFuAZnA">

        <span data-raseType="RequirementSection" id="R3">Other than for some <span data-raseType="Exception" id="e3" data-raseProperty="small">small</span>
                    <span data-raseType="Selection" id="s31" data-raseProperty="building">buildings</span> / <span data-raseType="Selection" id="s32" data-raseProperty="premise">premises</span>, an <span data-raseType="Requirement" id="r3" data-raseProperty="electrically operated fire alarm system">electrically operated fire alarm system</span> should be provided.</span>
            In some situations, the alarm should be operated by a fire detection system. The detailed
            specification should be compatible with the fire strategy for the building.</p>


            <p data-identifier="u7ekWVmAck6X7LGRbeT7pw" >
                    <b>NOTE:</b> The term 'fire alarm system' describes the combination of components for giving an
               audible and/or other perceptible warning of fire.
            </p>
                <p data-identifier="T1l14M_kn0KZ-syP3XTXzQ" >
                    <b>NOTE:</b> In this document, the term 'fire detection system' describes any type of automatic
               sensor network and associated control and indicating equipment. Sensors may be sensitive
               to smoke, heat, gaseous combustion products or radiation. Automatic sprinkler systems
               can also be used to operate a fire alarm system.
            </p>
                <p  data-numbered="global" data-identifier="huTMFRZ0akWlcQhrh8L9Ow">
                    <span data-raseType="RequirementSection" id="R4">In '<span data-raseType="Selection" id="s41" data-raseProperty="purpose group" data-raseTarget="2(a)">residential (institutional)</span>' and '<span data-raseType="Selection" id="s42" data-raseProperty="purpose group" data-raseTarget="2(b)">residential (other)</span>' occupancies (purpose groups
               2(a) and 2(b)), <span data-raseType="Requirement" id="r41" data-raseProperty="automatic fire detection count" data-raseComparator="greaterthan" data-raseTarget="0" data-raseUnit="number">automatic fire detection</span> and <span data-raseType="Requirement" id="r42" data-raseProperty="automatic fire alarm count" data-raseComparator="greaterthan" data-raseTarget="1" data-raseUnit="number">alarms</span> should be provided.</span>
                </p>
                <p  data-numbered="global" data-identifier="550s76ate0SF_oZ3JN5otA">
                    <span data-raseType="RequirementSection" id="R5">
                        <span data-raseType="Requirement" id="r51" data-raseProperty="automatic fire detection count" data-raseComparator="greaterthan" data-raseTarget="0" data-raseUnit="number">Automatic fire detection</span> and <span data-raseType="Requirement" id="r52" data-raseProperty="automatic fire alarm count" data-raseComparator="greaterthan" data-raseTarget="1" data-raseUnit="number">alarms</span> should be provided in <span data-raseType="Application" id="a51" data-raseProperty="building">non-residential
               occupancies</span> where a fire could break out in an <span data-raseType="Selection" id="s51" data-raseProperty="occupancy" data-raseTarget="unoccupied">unoccupied</span>
                        <span data-raseType="Application" id="a52" data-raseProperty="part of premise">part of the premises</span> (e.g.
               <span data-raseType="Selection" id="s52" data-raseProperty="occupancy" data-raseTarget="storage">a storage area</span> or a part of the building that is <span data-raseType="Selection" id="s53" data-raseProperty="visited" data-raseComparator="notequalto" data-raseTarget="regulary">not visited on a regular basis</span>) and
               <span data-raseType="Application" id="a54" data-raseProperty="means-of-escape" data-raseTarget="vulnerable"> prejudice the means of escape from occupied part(s)</span> of the premises.</span>
                </p>
                <p data-numbered="global" data-identifier="h8MSsgQkvU6RRDTTzxKwUg">
                    <span data-raseType="RequirementSection" id="R6">
                        <span data-raseType="Requirement" id="r6" data-raseProperty="automatic fire detection count" data-raseComparator="greaterthan" data-raseTarget="0" data-raseUnit="number">Automatic fire detection</span> will also be necessary where <span data-raseType="Selection" id="s61" data-raseProperty="automatic fire protection systems count" data-raseComparator="greaterthan" data-raseTarget="0" data-raseUnit="number">fire protection systems</span>, such
               as <span data-raseType="Selection" id="s62" data-raseProperty="automatic pressure differential system count" data-raseComparator="greaterthan" data-raseTarget="0" data-raseUnit="number">pressure differential systems</span> or <span data-raseType="Selection" id="s63" data-raseProperty="automatic door releases count" data-raseComparator="greaterthan" data-raseTarget="0" data-raseUnit="number">door releases</span>, need to operate automatically.</span>
                </p>
                <p data-numbered="global" data-identifier="af3taAqEYU-DkcaeiCbC8g">Every building design should be assessed individually. General guidance on the category
               of fire detection system that may need to be provided within a building can be found
               in Table A1 of<b>BS 5839-1</b>.
            </p>
                <p data-numbered="global" data-identifier="hBkTxRAu2kqMhFa4PqwRkQ">
                    <span data-raseType="RequirementSection" id="R7">Where an <span data-raseType="Application" id="a7" data-raseProperty="electrically operated fire detection and alarm system">electrically operated fire detection and alarm system</span> is provided, it should
               <span data-raseType="Requirement" id="r7" data-raseProperty="BS 5839-1 compliant">comply  with <b>BS 5839-1</b>
                        </span>.</span>
                </p>
                <p data-numbered="global" data-identifier="UoQ_AdpOm0-cK5AJ2UVwSQ">
                    <b>BS 5839-1</b> specifies three categories of system:
            </p>
                <ol>
                    <li data-identifier="Bf1KdRrb2EiFflZapGhrRA"> Category L - for the protection of life.</li>
                    <li data-identifier="KDCqdEGESki823-V9IkuEQ"> Category M - manual fire detection and alarm systems</li>
                    <li data-identifier="RpueNxvWHkueD8bsp6ltcA"> Category P - for property protection. </li>
                </ol>
                <p data-identifier="wYoKsYHkNka2ibh5KJlshw" >Category L systems are divided into the following.</p>
                <p data-identifier="E0EFufdNMECtSQiDKDDnBA" >L1 - systems installed throughout the protected building.</p>
                <p data-identifier="lp_9nUdqvUKImtUJd2n0eg" >L2 - systems installed only in defined parts of the protected building (a category
               L2 system will normally include the coverage required of a category L3 system).
            </p>
                <p data-identifier="TJEFo5AwRUmQM5ykyxfKKw" >L3 - systems designed to warn of fire at an early enough stage to enable all occupants,
               other than possibly those in the room where the fire started, to escape safely before
               the escape routes become impassable because of fire, smoke or toxic gases.
            </p>
                <p data-identifier="-BsAwDITzUinQW3PaNTwng" >L4 - systems installed within those parts of the escape routes that comprise circulation
               areas and circulation spaces, such as corridors and stairs.
            </p>
                <p data-identifier="0BRvFATBSUiZjVTA8zudFg" >L5 - systems in which the protected area(s) and/or the location of detectors are designed
               to satisfy a specific fire safety objective (other than that of a category L1, L2,
               L3 or L4 system).
            </p>
                <p data-identifier="9Hj7A1FiXUaVUlxSXOQVWg" >Type P systems are divided into the following.</p>
                <p data-identifier="pdHkxx7RHE-244oiwY9iJA" >P1 - systems installed throughout the protected building.</p>
                <p data-identifier="UYR95RJHAEyTX352kIbk3A" >P2 - systems installed only in defined parts of the protected building.</p>
            </section>
        </section>
    </body>
</html>

JSON Example

{
    "dcterms:subject": ["Uniclass2015: Circulation and storage entities"],
    "dcterms:type": "Guidance",
    "dcterms:coverage.spatial": "GB-ENG",
    "ckterms:sector": ["Uniclass2015: Circulation and storage entities"],
    "dcterms:coverage.temporal": "2020-11-26",
    "dcterms:title": "The Building Regulations 2010 - Fire Safety - Approved Document B  - Volume 2: Buildings\n         other than dwellings\n      ",
    "dcterms:modified": "2020-11-26",
    "ckterms:version": "1.0",
    "dcterms:dateCreated": "2019-01-01",
    "dcterms:identifier": "hJJ3qCORuUmX8LWK0_SZQQ",
    "ckterms:projectStage": "CIC 4 : Technical design",
    "ckterms:accessLocation": "TBC",
    "dcterms:language": "en-gb",
    "sections": [{
        "dcterms:identifier": "hSGB1-fufEiacSuJk8k62g",
        "numbered": "global",
        "dcterms:title": "Fire detection and alarm systems",
        "sections": [{
            "dcterms:identifier": "xwvgHCgydk2g0xOXFUUBDg",
            "dcterms:title": "General provisions",
            "paragraphs": [{
                "dcterms:identifier": "XhhBpnB4OEK7hIT65pL2Dg",
                "numbered": "global",
                "body": "<span data-raseType=\"RequirementSection\" id=\"R1\">All <span data-raseProperty=\"building\" data-raseType=\"Application\" id=\"a1\">buildings</span> should have arrangements for <span data-raseProperty=\"fire detecting arrangements\" data-raseType=\"Requirement\" id=\"r11\">detecting fire</span> and <span data-raseProperty=\"arrangements for raising the alarm\" data-raseType=\"Requirement\" id=\"r12\">raising the alarm</span>. </span> In most buildings, fires are detected by people, either by sight or smell, and therefore often nothing more is needed."
            }, {
                "dcterms:identifier": "mmIg3jdJQkmPzlyZVjPE7g",
                "numbered": "global",
                "body": "In some small buildings/premises, the means of raising the alarm may be simple (for example,a shouted warning). In assessing appropriate solutions, warnings need to be heard and understood throughout the premises."
            }]
        }, {
            "dcterms:identifier": "MSriiQXQn0uDeengQVGHLA",
            "dcterms:title": "Fire detection and alarm systems",
            "paragraphs": [{
                "dcterms:identifier": "KKS5C-JUdUOJBvGxFuAZnA",
                "numbered": "global",
                "body": "<span data-raseType=\"RequirementSection\" id=\"R3\">Other than for some <span data-raseProperty=\"small\" data-raseType=\"Exception\" id=\"e3\">small</span><span data-raseProperty=\"building\" data-raseType=\"Selection\" id=\"s31\">buildings</span> / <span data-raseProperty=\"premise\" data-raseType=\"Selection\" id=\"s32\">premises</span>, an <span data-raseProperty=\"electrically operated fire alarm system\" data-raseType=\"Requirement\" id=\"r3\">electrically operated fire alarm system</span> should be provided.</span> In some situations, the alarm should be operated by a fire detection system. The detailed specification should be compatible with the fire strategy for the building."
            }, {
                "dcterms:identifier": "u7ekWVmAck6X7LGRbeT7pw",
                "body": "<b>NOTE:</b> The term 'fire alarm system' describes the combination of components for giving an audible and/or other perceptible warning of fire."
            }, {
                "dcterms:identifier": "T1l14M_kn0KZ-syP3XTXzQ",
                "body": "<b>NOTE:</b> In this document, the term 'fire detection system' describes any type of automatic sensor network and associated control and indicating equipment. Sensors may be sensitive to smoke, heat, gaseous combustion products or radiation. Automatic sprinkler systems can also be used to operate a fire alarm system."
            }, {
                "dcterms:identifier": "huTMFRZ0akWlcQhrh8L9Ow",
                "numbered": "global",
                "body": "<span data-raseType=\"RequirementSection\" id=\"R4\">In '<span data-raseProperty=\"purpose group\" data-raseTarget=\"2(a)\" data-raseType=\"Selection\" id=\"s41\">residential (institutional)</span>' and '<span data-raseProperty=\"purpose group\" data-raseTarget=\"2(b)\" data-raseType=\"Selection\" id=\"s42\">residential (other)</span>' occupancies (purpose groups 2(a) and 2(b)), <span data-raseComparator=\"greaterthan\" data-raseProperty=\"automatic fire detection count\" data-raseTarget=\"0\" data-raseType=\"Requirement\" data-raseUnit=\"number\" id=\"r41\">automatic fire detection</span> and <span data-raseComparator=\"greaterthan\" data-raseProperty=\"automatic fire alarm count\" data-raseTarget=\"1\" data-raseType=\"Requirement\" data-raseUnit=\"number\" id=\"r42\">alarms</span> should be provided.</span>"
            }, {
                "dcterms:identifier": "550s76ate0SF_oZ3JN5otA",
                "numbered": "global",
                "body": "<span data-raseType=\"RequirementSection\" id=\"R5\"><span data-raseComparator=\"greaterthan\" data-raseProperty=\"automatic fire detection count\" data-raseTarget=\"0\" data-raseType=\"Requirement\" data-raseUnit=\"number\" id=\"r51\">Automatic fire detection</span> and <span data-raseComparator=\"greaterthan\" data-raseProperty=\"automatic fire alarm count\" data-raseTarget=\"1\" data-raseType=\"Requirement\" data-raseUnit=\"number\" id=\"r52\">alarms</span> should be provided in <span data-raseProperty=\"building\" data-raseType=\"Application\" id=\"a51\">non-residential occupancies</span> where a fire could break out in an <span data-raseProperty=\"occupancy\" data-raseTarget=\"unoccupied\" data-raseType=\"Selection\" id=\"s51\">unoccupied</span><span data-raseProperty=\"part of premise\" data-raseType=\"Application\" id=\"a52\">part of the premises</span> (e.g. <span data-raseProperty=\"occupancy\" data-raseTarget=\"storage\" data-raseType=\"Selection\" id=\"s52\">a storage area</span> or a part of the building that is <span data-raseComparator=\"notequalto\" data-raseProperty=\"visited\" data-raseTarget=\"regulary\" data-raseType=\"Selection\" id=\"s53\">not visited on a regular basis</span>) and <span data-raseProperty=\"means-of-escape\" data-raseTarget=\"vulnerable\" data-raseType=\"Application\" id=\"a54\"> prejudice the means of escape from occupied part(s)</span> of the premises.</span>"
            }, {
                "dcterms:identifier": "h8MSsgQkvU6RRDTTzxKwUg",
                "numbered": "global",
                "body": "<span data-raseType=\"RequirementSection\" id=\"R6\"><span data-raseComparator=\"greaterthan\" data-raseProperty=\"automatic fire detection count\" data-raseTarget=\"0\" data-raseType=\"Requirement\" data-raseUnit=\"number\" id=\"r6\">Automatic fire detection</span> will also be necessary where <span data-raseComparator=\"greaterthan\" data-raseProperty=\"automatic fire protection systems count\" data-raseTarget=\"0\" data-raseType=\"Selection\" data-raseUnit=\"number\" id=\"s61\">fire protection systems</span>, such as <span data-raseComparator=\"greaterthan\" data-raseProperty=\"automatic pressure differential system count\" data-raseTarget=\"0\" data-raseType=\"Selection\" data-raseUnit=\"number\" id=\"s62\">pressure differential systems</span> or <span data-raseComparator=\"greaterthan\" data-raseProperty=\"automatic door releases count\" data-raseTarget=\"0\" data-raseType=\"Selection\" data-raseUnit=\"number\" id=\"s63\">door releases</span>, need to operate automatically.</span>"
            }, {
                "dcterms:identifier": "af3taAqEYU-DkcaeiCbC8g",
                "numbered": "global",
                "body": "Every building design should be assessed individually. General guidance on the category of fire detection system that may need to be provided within a building can be found in Table A1 of<b>BS 5839-1</b>."
            }, {
                "dcterms:identifier": "hBkTxRAu2kqMhFa4PqwRkQ",
                "numbered": "global",
                "body": "<span data-raseType=\"RequirementSection\" id=\"R7\">Where an <span data-raseProperty=\"electrically operated fire detection and alarm system\" data-raseType=\"Application\" id=\"a7\">electrically operated fire detection and alarm system</span> is provided, it should <span data-raseProperty=\"BS 5839-1 compliant\" data-raseType=\"Requirement\" id=\"r7\">comply with <b>BS 5839-1</b></span>.</span>"
            }, {
                "dcterms:identifier": "UoQ_AdpOm0-cK5AJ2UVwSQ",
                "numbered": "global",
                "body": "<b>BS 5839-1</b> specifies three categories of system:"
            }, {
                "dcterms:identifier": "wYoKsYHkNka2ibh5KJlshw",
                "body": "Category L systems are divided into the following."
            }, {
                "dcterms:identifier": "E0EFufdNMECtSQiDKDDnBA",
                "body": "L1 - systems installed throughout the protected building."
            }, {
                "dcterms:identifier": "lp_9nUdqvUKImtUJd2n0eg",
                "body": "L2 - systems installed only in defined parts of the protected building (a category L2 system will normally include the coverage required of a category L3 system)."
            }, {
                "dcterms:identifier": "TJEFo5AwRUmQM5ykyxfKKw",
                "body": "L3 - systems designed to warn of fire at an early enough stage to enable all occupants, other than possibly those in the room where the fire started, to escape safely before the escape routes become impassable because of fire, smoke or toxic gases."
            }, {
                "dcterms:identifier": "-BsAwDITzUinQW3PaNTwng",
                "body": "L4 - systems installed within those parts of the escape routes that comprise circulation areas and circulation spaces, such as corridors and stairs."
            }, {
                "dcterms:identifier": "0BRvFATBSUiZjVTA8zudFg",
                "body": "L5 - systems in which the protected area(s) and/or the location of detectors are designed to satisfy a specific fire safety objective (other than that of a category L1, L2, L3 or L4 system)."
            }, {
                "dcterms:identifier": "9Hj7A1FiXUaVUlxSXOQVWg",
                "body": "Type P systems are divided into the following."
            }, {
                "dcterms:identifier": "pdHkxx7RHE-244oiwY9iJA",
                "body": "P1 - systems installed throughout the protected building."
            }, {
                "dcterms:identifier": "UYR95RJHAEyTX352kIbk3A",
                "body": "P2 - systems installed only in defined parts of the protected building."
            }]
        }]
    }]
}